- The System should work on the principle of positive pressurization of the area served to maintain optimum IAQ levels.
- The System should work on the concept of mechanical/passive filtration achieved through multiple layers of filters.
- The System should improve the IAQ of the area by reducing concentrations of PM10, PM2.5, SOx, NOx, O3, VOCs and CO2.
- All pollutant levels should be aimed to be well below ISHRAE/ASHRAE Standards
- After Commissioning of the System, it should guarantee to achieve a minimum of 90% reduction inside the served space as compared to ambient, and above 99% reduction at the discharge of the unit.
- The reductions can be achieved within 3-4 hours of running the System provided all windows and/or doors are closed.
- The daily average for PM2.5 levels is below 25 µg /m3 (micrograms per cubic meter).
- Should have provision to intake fresh air
- It should keep TVOCs values below 500 µg /m3 which is as per RESET
- The System must be designed in such a way that levels of CO2 should be below 800 ppm, provided the occupancy in the building does not go beyond the planned and designed density.